Leave Your Message
RGW1 Type Three Pole Outdoor Disconnector With Fuse-bases
Disconnect Switch

RGW1 Type Three Pole Outdoor Disconnector With Fuse-bases

    product detail

    Product Details

    RGW1 Type Three Pole Outdoor Disconnector With Fuse-bases

    Summary

    RGW1-24 series three pole outdoor disconnector with fuse-bases is the high voltage switch equipment, in the suitable for outdoor 24kV line internet with voltage and no load, to make separate and fabricate. With CS8 type manpower operate machinery to avoid earth line with power and composite flash-locks and wrong operate. The operator no need put another earth line. Pollution-proof type isolate switch of customer in filthy conduction area. It can solve the pollution of shed when it is work.

    Definition of model

    Rated current

    Rated voltage

    Design No.

    Outdoor type

    Disconnector with fuse

    Service condition

    1.The altitude above sea level: 2000m.

    2.The ambient air temperatures: -40 to 40

    3.Wind speed doesn't exceed 700Pa (not exceed 34m/s)

    4.The earthquake intensity doesn't exceed 8 degrees.

    5.The working situation: without frequent violent vibration.

    6.The installation site of ordinary type isolator should be kept away from gas, smoke chemical deposition, salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction capability of the isolator.

    7.Pollution proof type isolator applies to sever filthy conduction area. However, it shouldn't be any explosive matters and matters causing fire.

    图片1.png

    Overall And Installation Dimension

    图片8.png

    RGW-B 11-33kV

    Type

    Rated Voltage(kV)

    Rated Current(A)

    4s Heat Steady Current(A)

    Shock Steady Current(A)

    Impulse Withstand Voltage(kV)

    Power-Frequency Withstand Voltage(kV)

    RGW-B

    11

    400

    12500

    31500

    95

    42

    RGW-B

    33

    600

    12500

    31500

    195

    80

    12-15kV

    Type

    Rated Voltage(kV)

    Rated Current(A)

    4s Heat Steady Current(A)

    Shock Steady Current(A)

    Impulse Withstand Voltage(kV)

    Power-Frequency Withstand Voltage(kV)

    To earth

    Across the isolating distance

    To earth

    Across the isolating distance

    GW9-12W/400

    12

    400

    12500

    31500

    75

    85

    38

    42

    GW9-12W/630

    12

    630

    12500

    31500

    75

    85

    38

    42

    GW9-12W/1250

    12

    1250

    20000

    50000

    75

    85

    38

    42

    12-15kV

    Type

    Rated Voltage(kV)

    Rated Current(A)

    Limit Passing Current(kA)

    10 sec Heat Stabilization Current(A)

    Reak Value

    r.m.s

    GW9-10

    10,12,15

    200

    5

    9

    5

    GW9-12

    10,12,15

    400

    21

    15

    10

    GW9-15

    10,12,15

    600

    35

    25

    14

    10,12,15

    1000

    50

    35

    20

    12-15kV

    Type

    Rated Voltage(kV)

    Rated Current(A)

    4s Heat Steady Current(A)

    Shock Steady Current(A)

    Impulse Withstand Voltage(kV)

    Power-Frequency Withstand Voltage(kV)

    To earth

    Across the isolating distance

    To earth

    Across the isolating distance

    HGW9-12W400

    12-15

    400

    12500

    31500

    75

    85

    38

    42

    HGW9-12W630

    12-15

    630

    12500

    31500

    75

    85

    38

    42

    500V

    Type

    Rated Voltage(kV)

    Rated Current(A)

    Breaking Current(A)

    JDW2-500

    500

    500

    30-500

    JDW2-800

    500

    800

    30-500

    HGWR1/GWR1 0.5-1600V

    Fuse Rated Current

    120A

    150A

    220A

    300A

    360A

    470A

    600A

    Fuse Specification

    0.15

    0.20

    0.30

    0.50

    0.60

    0.80

    0.90

    Transformer Volume

    80

    100

    150

    180-220

    250

    315-320

    400