Medium Voltage Heat Shrinkable Termination& Straight Joint Accessories
Heat Shrink Joint and Termination

Medium Voltage Heat Shrinkable Termination& Straight Joint Accessories

    product detail

    Product Details

    Medium Voltage Heat Shrinkable Termination& Straight Joint Accessories

    Medium Voltage Heat Shrinkable Termination Accessories

    Heat shrinkable termination& straight joint accessories are suitable for up to 11/20/35kV, insulated with PVC,XLPE and PE polymeric cables.

    Feature

    1.Reliable stress control

    2.Large cross-section range

    3.Excellent corrosion resistance

    4.UV resistance and weathering resistance

    5.Anti-tracking

    6.Superior electrical and mechanical properties

    7.Easy installation

    1591856740142984.jpg

    Performance of 11KV

    Test

    Requirement

    Power frequency withstand voltage 1min

    45kV,No flashover, no breakdown

    Partial discharge

    ≤10PC at 13kV

    Heating cycles in air

    22kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles

    Impluse voltage (peak)

    105kV,No flashover, no breakdown

    Negative DC voltage 15 min

    52kV, No flashover, no breakdown

    Power frequency withstand voltage 4h

    35kV, No flashover, no breakdown

    Performance of 20KV

    Test

    Requirement

    Power frequency withstand voltage 1min

    75kV,No flashover, no breakdown

    Partial discharge

    ≤10PC at 27kV

    Heating cycles in air

    45kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles

    Impluse voltage (peak)

    170kV,No flashover, no breakdown

    Negative DC voltage 15 min

    108kV, No flashover, no breakdown

    Power frequency withstand voltage 4h

    72kV, No flashover, no breakdown

    Performance of 35KV

    Test

    Requirement

    Indoor moisture

    32.5kV,300h,No flashover, no breakdown

    Outdoor salt fog

    32.5kV,1000h,No flashover, no breakdown

    Partial discharge

    ≤10PC at 45kV

    Heating cycles in air

    65kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles

    AC voltage withstand 1min

    104kV, No flashover, no breakdown

    DC voltage withstand 15min

    104kV, No flashover, no breakdown

    AC voltage withstand 5min

    117kV, No flashover, no breakdown

    Impluse voltage (peak)

    200kV,No flashover, no breakdown