Leave Your Message
Heat Shrink Bus-bar Insulation Tubing
Heat Shrink Joint and Termination

Heat Shrink Bus-bar Insulation Tubing

    product detail

    Product Details

    Heat Shrink Bus-bar Insulation Tubing

    Application

    Used in medium voltage substations up to 36kV to reduce electric clearance and increase insulation between bus-bars

    Feature

    1.Anti-tracking

    2.Excellent corrosion resistance

    3.UV resistance and weathering resistance

    4.Superior electrical and mechanical propertiesperformance.

    图片1.png

    Performance

    Test

    Test Method

    Requirement

    Tensile strength

    ASTM D 2671

    ≥11.8MPa

    Elongation at break

    ASTM D 2671

    700%

    tensile strength after heat aging

    ASTM D 2671/120℃,168小h

    ≥10MPa

    Elongation at break after heat aging

    ASTM D 2671/120℃,168h

    ≥500%

    Longitudinal shrinkage

    ASTM D 2671

    0 to-10%

    Electrical strength

    IEC 243

    ≥20KV/mm

    Dielectric constant

    IEC 250

    3.0 Max

    Volume resistivity

    IEC 93

    1013Ω.cm

    Flame retardancy (oxygen index)

    ASTM 4589

    ≥25

    Copper corrosive 120 ° C, 168 hours

    ASTM D 2671

    Pass

    Low temperature brittleness -40 ° C, 4 hours

    ASTM D 2671

    No crack

    Water absorption rate

    ISO 62/23℃,14 days

    ≤0.5%