    GN19-12(C) Indoor High Voltage Isolate Switch

    Summary

    GN19- 12(C) indoor disconnecting switch is applied in power system with rated voltage 12kV, AC 50Hz and below, it uses with CS6-1 manual operating mechanism, for making and breaking the circuit with voltage and without load, it has pollution proof type, plateau type and adding electrification indication type.

    Definition of model

    Add power display device

    G- Plateaux type W-Antifouling type

    Rated current

    Wall type: C1-turn at the side of wall

    C2-break at the side of wall

    C3-Both sides at the side of wall

    Rated voltage

    Design number

    Indoor type

    Isolate switch

    Service condition

    1.The altitude above sea level: 2000m.

    2.The ambient air temperatures: -40 to 40℃.

    3.Wind speed doesn't exceed 700Pa (not exceed 34m/s).

    4.The earthquake intensity doesn't exceed 8 degrees.

    5.The working situation: without frequent violent vibration.

    6.The installation site of ordinary type isolator should be kept away from gas, smoke chemical deposition, salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction capability of the isolator.

    7.Pollution proof type isolator applies to sever filthy conduction area. However, it shouldn't be any explosive matters and matters causing fire.

    G19 Key Technical Parameters

    Items

    Units

    Technical parameters

    Rated voltage

    kV

    12-15

    1 min Power frequency withstand voltage

    To earth

    kV

    38

    Across open DS

    kV

    42

    Lightning impulse withstand voltage

    To earth

    kV

    75

    Across open DS

    kV

    85

    Rated frequency

    Hz

    50

    Rated current

    A

    200、400/630/1000/1250

    Short time withstand current(4s)

    kA

    6.3/12.5/20/31.5/40

    Rated peak withstand current

    kA

    16/31.5/50/80/100

    Rated duration of short/circuit

    S

    4/2

    Creepage Distance

    mm

    300-380

    Mechanical life

    times

    2000

    Type

    Rated Voltage(kV)

    Rated Current(A)

    Short time withstand current(4s) kV

    Rated peak withstand current kV

    GN119-12/400-12.5

    12

    400

    12.5

    31.5

    GN19-12/630-20

    12

    630

    20

    50

    GN19-12/1000-31.5

    12

    1000

    31.5

    80

    GN19-12/1250-31.5

    12

    1250

    31.5

    80

    GN19-12/400-12.5

    12

    400

    12.5

    31.5

    GN19-12/630-20

    12

    630

    20

    50

    GN19-12/1000-31.5

    12

    1000

    31.5

    80

    GN19-12/1250-31.5

    12

    1250

    31.5

    80