Leave Your Message
GN1-12G(D) Series Outdoor High Voltage Isolate
Disconnect Switch

GN1-12G(D) Series Outdoor High Voltage Isolate

brand: YOJIU model: SV

    product detail

    Product Details

    GN1-12G(D) Series Outdoor High Voltage Isolate

    GW1-12G(D)

    Summary

    GN1-12G(D) series outdoor high voltage isolate switch is the high voltage switch equipment of composite structure, it is suitable for outdoor 12kV line net with voltage and no load to make opening and close. With CS □ type manpower operate machinery, can avoid earth line with power and composite flash-locks, wrong operate. The operator is no need to put another earth line. Pollution-proof type isolate switch satisfy customer in filthy conduction area. It can solve the pollution of shed when it is working.

    Definition of model

    Rated short time withstand current

    Rated current

    Earth contrivance

    Plateau type

    Rated voltage

    Design No

    Outdoor type

    Isolating switch

    Service condition

    1.The altitude above sea level: 2000m.

    2.The ambient air temperatures: -40 to 40

    3.Wind speed doesn't exceed 700Pa (not exceed 34m/s)

    4.The earthquake intensity doesn't exceed 8 degrees.

    5.The installation site of ordinary type isolator should be kept away from gas, smoke chemical deposition, salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction capability of the isolator.

    6.Pollution proof type isolator applies to sever filthy conduction area. However, it shouldn't be any explosive matters and matters causing fire.

    GW1 Key Technical Parameters

    Items

    Units

    Technical parameters

    Rated voltage

    kV

    10

    15

    20

    Max. operating voltage

    12

    17.5

    24

    1 min Power frequency withstand voltage

    To earth

    kV

    38

    42

    50

    Across open DS

    kV

    42

    48

    60

    Lightning impulse withstand voltage

    To earth

    kV

    75

    105

    125

    Across open DS

    kV

    85

    120

    145

    Rated frequency

    Hz

    50

    Rated current

    A

    200

    400

    630

    1250

    Short time withstand current(4s)

    kA

    6.3

    12.5

    20

    31.5

    Rated peak withstand current

    kA

    10

    31.5

    50

    80

    Mechanism supplied for disconnector

    CS8-1、CS8-D、CD8-8 Rain type manual mechanism or CX6 motor drive mechanism

    HGW1 Key Technical Parameters

    Items

    Units

    Technical parameters

    Rated voltage

    kV

    12

    24

    33

    Max. operating voltage

    15

    27

    35

    1 min Power frequency withstand voltage

    To earth

    kV

    40

    50

    80

    Across open DS

    kV

    47

    60

    90

    Lightning impulse withstand voltage

    To earth

    kV

    105

    125

    180

    Across open DS

    kV

    120

    145

    210

    Rated frequency

    Hz

    50

    Rated current

    A

    200

    400

    630

    1250

    Short time withstand current(4s)

    kA

    6.3

    12.5

    20

    31.5

    Rated peak withstand current

    kA

    16

    31.5

    50

    80

    Mechanism supplied for disconnector

    CS8-1、CS8-D、CD8-8 Rain type manual mechanism or CX8-5 motor drive mechanism

    Overall And Installation Dimension

    图片3.png

    Product model number

    A

    B

    C

    GW1-12G/400A

    510

    555

    18×24=4

    GW1-12G/630A

    530

    555

    GW1-24G/400A

    510

    555

    18×24=4

    GW1-24G/630A

    530

    555